Home » Meger Test Low Insulation Problem Alarm ASL Scorpio

Meger Test Low Insulation Problem Alarm ASL Scorpio

Meger Test Low Insulation Problem Alarm ASL Scorpio

Specification:

Equipment

  1. Panel AC230 Incoming and Feeder.
  2. Panel AC230 Feeder.
  3. Panel No. 1 AC440 Feeder

Error Issue:

  1. Low Insulation on the panel AC230 Incoming and Feeder
  2. Low Insulation on the panel AC230 Feeder.
  3. Low Insulation on the panel No. 1 AC440 Feeder.

Action Taken

  1. Checking on all feeder panel output AC230 Incoming and Feeder.
  2. Checking on all feeder panel output AC230 Feeder.
  3. Checking on all feeder panel output No. 1 AC440 Feeder.
  4. Checking on all terminal connections ship equipment, including: all lights, switches, electronic equipment, kitchenware, etc.

Solution Resulting:

  • Obtained conditions of low insulation on the connection to the kitchen equipment. Solution:
    • Replacement unit heater on the hot plate.
    • Replacement cables to the unit heater.
  • Obtained conditions of low insulation on the connection to the spotlight lamp installation.
    • Floodlight consists of 10 units must be replaced.
    • Spotlight consists of 2 units to be replaced.
    • All cable lines for lights called in point A and B should be replaced.
Transformateur Unit for Spotlight / Floodlight
Transformateur Unit for Spotlight / Floodlight
Spotlight unit
Spotlight unit
  • Results megger test (with the condition to disconnect the installation of lights at points A and B)
Results megger test R to S (1)
Results megger test R to S (1)
Results megger test R to S (2)
Results megger test R to S (2)
Results megger test R to T (1)
Results megger test R to T (1)
Results megger test R to T (2)
Results megger test R to T (2)
Results megger test T to S (1)
Results megger test T to S (1)
Results megger test T to S (2)
Results megger test T to S (2)
Results megger test R to Ground (1)
Results megger test R to Ground (1)
Results megger test R to Ground (2)
Results megger test R to Ground (2)
Results megger test S to Ground (1)
Results megger test S to Ground (1)
Results megger test S to Ground (2)
Results megger test S to Ground (2)
Results megger test T to Ground (1)
Results megger test T to Ground (1)
Results megger test T to Ground (2)
Results megger test T to Ground (2)

Documentation

Appointment of indicators insulation meter before the repair
Appointment of indicators insulation meter before the repair
Appointment of indicators insulation meter after the repair on panel AC230 Incoming and Feeder.
Appointment of indicators insulation meter after the repair on panel AC230 Incoming and Feeder.
Appointment of indicators insulation meter after the repair on panel AC230 Feeder
Appointment of indicators insulation meter after the repair on panel AC230 Feeder
Appointment of indicators insulation meter after the repair on panel AC440 Feeder.
Appointment of indicators insulation meter after the repair on panel AC440 Feeder.

Leave a Reply