Check and Service CO2 ASL Scorpio

Specification:

  • CO2 Control Monitor
  • Equipment CO2 Panel Controls

Error Issue:

  • Damage of Box CO2, including :
    • Part Lock,
    • Hinges.
  • Damage of limit switch Box.
  • Requires testing the alarm function when the CO2 gas is used.

Action Taken

  • Removing the old box, pipe gas installation and wiring installation.
  • Replacement with a new box.
    • Installing locking support.
    • Removing components panel from the old box to the new box.
  • Installation new box, pipe gas installation, wiring installation and connection back.
  • Test perform with crew.

Solution Resulting:

  1. Door sensing are function properly.
  2. There are no leak in the gas pipe connection,
  3. The alarm function is running normally.
  4. Interconnection to external device are function well.
  5. Pressure switch function in gas pipe system CO2 has been improved and it work well.

Documentation

Old Panel Boxs
Old Panel Boxs
Panel Components
Panel Components
Wiring Schema CO2 Alarm System
Wiring Schema CO2 Alarm System
Pressure Switch Position
Pressure Switch Position
Gas Pipe Installation
Gas Pipe Installation
Old Panel Boxs
Old Panel Boxs

Materi Job :